Design calculators
Quick checks for everyday layout work. Inputs are in mm, bar and °C; results show both unit systems where useful.
Calculation verification
Every result on this page can be checked by hand. For each calculator: the inputs, the formula, a worked example with real numbers, the units, the standard it comes from, and what it does not cover. Worked examples checked against the calculator output on 17 Nov 2026.
Pipe wall thicknessASME B31.3 Eq. (3a)
Input parameters
| Parameter | Symbol | Unit | Source |
|---|---|---|---|
| Nominal pipe size | NPS → D | mm | Outside diameter from ASME B36.10M / B36.19M |
| Design pressure | P | bar(g), used as MPa (÷ 10) | Your design basis |
| Allowable stress | S | MPa | B31.3 Table A-1M, for your material, grade and design temperature (entered by you) |
| Quality factor | E | – | B31.3 Table A-1B |
| Weld strength reduction factor | W | – | B31.3 para. 302.3.5 |
| Coefficient | Y | – | B31.3 Table 304.1.1 (0.4 for ferritic steel below 482 °C) |
| Corrosion + thread allowance | c | mm | Piping class |
| Mill under-tolerance | m | % | Pipe specification (12.5% typical for seamless) |
Formula used
t = P · D / [ 2 (S · E · W + P · Y) ] pressure design thickness, Eq. (3a) tm = t + c minimum required thickness tn = tm / (1 − m/100) minimum nominal wall Pick the lightest listed schedule with wall ≥ tn. Valid only while t < D/6.
Worked example
NPS 6 carbon steel pipe, ASTM A106 Gr B seamless, design 40 bar(g) at 200 °C, corrosion allowance 1.5 mm, mill tolerance 12.5%.
- Inputs: D = 168.3 mm (B36.10M); P = 40 bar = 4.0 MPa
- S = 138 MPa (20.0 ksi): B31.3 Table A-1 basic allowable stress for A106 Gr B, constant up to 204 °C (400 °F). Confirm in your edition.
- E = 1.00 (seamless, Table A-1B); W = 1.00 (no longitudinal weld, below creep range); Y = 0.4 (ferritic steel below 482 °C, Table 304.1.1)
- t = 4.0 × 168.3 / [2 × (138 × 1.0 × 1.0 + 4.0 × 0.4)] = 673.1 / 279.2 = 2.41 mm
- tm = 2.41 + 1.5 = 3.91 mm
- tn = 3.91 / (1 − 0.125) = 4.47 mm
- D/6 = 28.0 mm, so t < D/6 and Eq. (3a) applies
- Lightest B36.10M wall listed for NPS 6 that is ≥ 4.47 mm: Sch STD / 40 = 7.11 mm
Result: Sch 40 (7.11 mm) passes; minimum nominal wall 4.47 mm.
Units
- Pressure entered in bar(g); 1 bar = 0.1 MPa
- Stress in MPa, lengths in mm
- Wall shown in mm and inch
Standard or engineering basis
- ASME B31.3 para. 304.1.2, Eq. (3a)
- Pipe dimensions: ASME B36.10M (carbon and alloy steel), B36.19M (stainless)
Assumptions and limitations
- Straight pipe under internal pressure only. Bends, branches, external pressure, and sustained, thermal or occasional loads are not checked.
- No allowable stress is built in. S, E, W and Y must come from your governing code edition.
- Not valid when t ≥ D/6 or P/(S·E) > 0.385; B31.3 then requires special consideration.
- Above 482 °C, Y and W depend on the material; check them.
- The piping class wall, not this result, is what you specify.
Flange class selectionASME B16.5 P–T ratings
Input parameters
| Parameter | Symbol | Unit | Source |
|---|---|---|---|
| Material group | – | – | B16.5 Table 1A: 1.1 carbon steel, 2.1 Type 304, 2.2 Type 316 |
| Design temperature | T | °C | Your design basis |
| Design pressure | P | bar(g) | Your design basis |
Formula used
Rating at T, linear interpolation between the two listed temperatures T₁ and T₂: p(T) = p₁ + (T − T₁) · (p₂ − p₁) / (T₂ − T₁) Selected class = lowest class with p(T) ≥ P
Worked example
Group 1.1 (A105), T = 250 °C, P = 40 bar(g).
- 250 °C is a listed temperature in B16.5 Table 2-1.1, so no interpolation is needed
- Class 150: 12.1 bar(g) < 40, too low
- Class 300: 41.9 bar(g) ≥ 40, OK
- Interpolation check at 225 °C, Class 300: 43.8 + (225 − 200) × (41.9 − 43.8) / (250 − 200) = 42.9 bar(g)
Result: Class 300 (41.9 bar(g) at 250 °C).
Units
- bar(g) and psig (1 bar = 14.5038 psi)
- °C and °F
Standard or engineering basis
- ASME B16.5 Table 2-1.1 (Group 1.1, metric). Groups 2.1 and 2.2 are interpolated in the °F tables and converted to bar.
- B16.5 allows linear interpolation between listed temperatures.
Assumptions and limitations
- Only Material Groups 1.1, 2.1 and 2.2 are included.
- The flange rating is not the joint rating: gasket, bolting and the pipe must also be adequate.
- NPS 26 and above (ASME B16.47) are not covered.
- Hydrotest pressure and short-term variations are not checked.
Elbow take-offBend geometry, ASME B16.9 radii
Input parameters
| Parameter | Symbol | Unit | Source |
|---|---|---|---|
| Nominal pipe size | NPS → OD, R | mm | B36.10M OD; B16.9 bend radius |
| Bend angle | θ | degrees | Routing |
| Radius type | R | – | LR = 1.5D, SR = 1D, 3D, 5D |
Formula used
Take-off (centre to end): A = R · tan(θ / 2) Centreline arc = R · θ (θ in radians) Outer arc = (R + OD/2) · θ; inner arc = (R − OD/2) · θ
Worked example
NPS 4 long-radius elbow, θ = 60°.
- R = 152.4 mm (6 in, B16.9 LR); OD = 114.3 mm; θ = 60° = 1.0472 rad
- A = 152.4 × tan 30° = 152.4 × 0.5774 = 88.0 mm
- Centreline arc = 152.4 × 1.0472 = 159.6 mm
- Outer arc = (152.4 + 57.15) × 1.0472 = 219.4 mm
- Inner arc = (152.4 − 57.15) × 1.0472 = 99.7 mm
Result: Take-off 88.0 mm (3.46 in).
Units
- mm and inch
- Angle in degrees
Standard or engineering basis
- ASME B16.9 centre-to-end dimensions and bend radii
- Plane geometry
Assumptions and limitations
- Weld root gaps are not included.
- 5D radius is taken as 5 × NPS (nominal), not 5 × actual OD.
- Cut elbows lose the B16.9 tangent and may need bevel preparation and NDE per your piping class.
Rolling offsetOffset geometry with LR elbows
Input parameters
| Parameter | Symbol | Unit | Source |
|---|---|---|---|
| Set (vertical offset) | S | mm | Layout |
| Roll (horizontal offset) | Ro | mm | Layout |
| Fitting angle | θ | degrees | 45°, 60°, 30°, 22.5° or 90° |
| Nominal pipe size | NPS → R | mm | B16.9 LR radius |
Formula used
True offset O = √(S² + Ro²) Travel T = O / sin θ; run = O / tan θ Elbow take-off A = R · tan(θ / 2) Pipe cut length = T − 2A; roll angle = atan(Ro / S)
Worked example
Set 600 mm, roll 450 mm, 45° LR elbows, NPS 4.
- O = √(600² + 450²) = 750.0 mm
- T = 750.0 / sin 45° = 750.0 / 0.7071 = 1060.7 mm
- Run = 750.0 / tan 45° = 750.0 mm
- A = 152.4 × tan 22.5° = 152.4 × 0.4142 = 63.1 mm
- Cut length = 1060.7 − 2 × 63.1 = 934.4 mm
- Roll angle = atan(450 / 600) = 36.9° from vertical
Result: Travel 1060.7 mm; pipe cut length 934.4 mm.
Units
- mm and inch
- Angles in degrees
Standard or engineering basis
- Right-angle trigonometry
- ASME B16.9 LR elbow radius (1.5 × NPS)
Assumptions and limitations
- Both fittings have the same angle and are long radius.
- Weld gaps are not deducted from the cut length.
- With 90° fittings the run is zero and only the true offset is given.
Pipe slopeSlope geometry
Input parameters
| Parameter | Symbol | Unit | Source |
|---|---|---|---|
| Horizontal length | L | mm | Layout |
| Slope | s | 1:N, %, mm/m or degrees | Process / project requirement |
| Start elevation | EL₁ | mm | Layout |
| End elevation | EL₂ | mm | Layout (when solving for slope or length) |
Formula used
s = 1/N or %/100 or (mm per m)/1000 or tan(angle) Drop H = L · s; EL₂ = EL₁ − H Slope s = (EL₁ − EL₂) / L; length L = H / s True (sloped) length = √(L² + H²)
Worked example
12 000 mm run at 1:100, starting at EL 105 000.
- s = 1/100 = 0.010
- H = 12 000 × 0.010 = 120.0 mm
- EL₂ = 105 000 − 120.0 = 104 880.0
- True length = √(12 000² + 120²) = 12 000.6 mm
- Angle = atan(0.010) = 0.573°; 1.000 %; 10.00 mm/m
Result: Drop 120.0 mm; end EL 104 880.0.
Units
- Lengths and elevations in mm
- Slope as 1:N, %, mm/m and degrees
Standard or engineering basis
- Plane geometry
Assumptions and limitations
- Straight run only.
- Sag between supports and support tolerances are not included; check the minimum slope your project sets for drains, flare and gravity lines.
Bolt lengthASME B16.5 flange and bolting data
Input parameters
| Parameter | Symbol | Unit | Source |
|---|---|---|---|
| Bolt type | – | – | Stud + 2 nuts, machine bolt, tap-end, wafer, tensioning |
| NPS and class | → tf, d, n | mm / in | ASME B16.5 flange thickness, bolt size and count |
| Gasket thickness × number | tg · ng | mm | Gasket standard |
| Item between flanges | w | mm | Wafer valve, blind, orifice |
| Thread engagement (tap-end) | e · d | mm | 1.0 d steel, 1.5 d cast iron |
| Projection past nut | k | threads | Project standard (3 typical) |
| Rounding | – | mm or in | Purchase increment |
Formula used
Stud bolt: L = 2·tf + 2·RF + ng·tg + w + 2·Hnut + 2·k·p Hnut = d (heavy hex); p = 25.4 / TPI; RF = 6.4 mm for Class 400 and up, 0 below Machine bolt: one nut and one projection; tap-end: one flange + engagement e·d Tensioning: + 1·d at one end. Round L up to the chosen increment.
Worked example
NPS 4 Class 300, stud bolts, spiral wound gasket 4.5 mm, 3 threads past each nut, round up to 5 mm.
- B16.5: tf = 1.19 in = 30.2 mm (includes the 1.6 mm raised face); 8 bolts, d = 3/4 in = 19.05 mm, 10 TPI → p = 2.54 mm
- Flanges 2 × 30.2 = 60.5 mm
- Gasket 4.5 mm
- Nuts 2 × 19.05 = 38.1 mm
- Projection 2 × 3 × 2.54 = 15.2 mm
- L = 60.5 + 4.5 + 38.1 + 15.2 = 118.3 mm → rounded up to 120 mm
Result: 8 × 3/4″-10 UNC × 120 mm stud bolts.
Units
- mm, with inch equivalents
- Thread pitch in mm and TPI
Standard or engineering basis
- ASME B16.5 flange thickness and bolting tables
- Heavy hex nut height ≈ d (ASME B18.2.2)
- Thread series ASME B1.1: UNC up to 1 in, 8UN above
Assumptions and limitations
- Nut height is taken as d, slightly more than the actual heavy hex nut, so the length is a little conservative.
- Washers, RTJ ring gaps, lens rings and spacers are not included unless entered as an item between flanges.
- The tensioning allowance is a typical 1 × d; use the tool maker's value.
- Where your project or vendor has a stud length table, that table governs.
Line spacing on a rackPipe OD and B16.5 flange OD
Input parameters
| Parameter | Symbol | Unit | Source |
|---|---|---|---|
| Line A and B: NPS | → OD | mm | ASME B36.10M |
| Line A and B: flange class | → F | mm | ASME B16.5 flange OD |
| Insulation thickness | ins | mm | Insulation specification |
| Clearance | cl | mm | Project standard (25 mm typical) |
Formula used
c1 = F_A/2 + OD_B/2 + ins_B + cl flange A next to line B c2 = F_B/2 + OD_A/2 + ins_A + cl flange B next to line A c3 = OD_A/2 + ins_A + OD_B/2 + ins_B + cl pipe next to pipe C–C = max(c1, c2, c3)
Worked example
Line A: NPS 6 Class 300, 50 mm insulation. Line B: NPS 4 Class 150, bare. Clearance 25 mm.
- OD_A = 168.3 mm; F_A = 12.5 in = 317.5 mm; OD_B = 114.3 mm; F_B = 9.0 in = 228.6 mm
- c1 = 158.8 + 57.2 + 0 + 25 = 240.9 mm
- c2 = 114.3 + 84.1 + 50 + 25 = 273.4 mm
- c3 = 84.1 + 50 + 57.2 + 0 + 25 = 216.3 mm
- C–C = 273.4 mm, governed by flange B next to insulated line A
Result: 273 mm C–C; round up to your rack module.
Units
- mm and inch
Standard or engineering basis
- Pipe OD: ASME B36.10M
- Flange OD: ASME B16.5
Assumptions and limitations
- Flanges are staggered: a flange never sits next to the other line's flange.
- Flanges are bare; add the box size if flanges are insulated.
- Shoes, guides, thermal movement and future lines are not included.
- NPS 26 and above (B16.47 flanges) are not covered here.
Unit converterExact conversion factors
Input parameters
| Parameter | Symbol | Unit | Source |
|---|---|---|---|
| Value | x | – | Your number |
| From unit | – | inch, mm, ft, m, bar, psi, MPa, kg/cm², °C, °F | – |
Formula used
1 in = 25.4 mm (exact); 1 ft = 304.8 mm 1 bar = 14.5038 psi = 0.1 MPa = 100 kPa; 1 kg/cm² = 0.980665 bar °F = °C × 9/5 + 32; K = °C + 273.15
Worked example
150 psi and 250 °C.
- 150 / 14.5038 = 10.342 bar
- 10.342 / 10 = 1.0342 MPa; 10.342 / 0.980665 = 10.546 kg/cm²
- 250 × 9/5 + 32 = 482 °F
Result: 150 psi = 10.342 bar; 250 °C = 482 °F.
Units
- As listed
Standard or engineering basis
- ISO 80000 / NIST SP 811 definitions
Assumptions and limitations
- Gauge and absolute pressure are not converted into each other; add about 1.013 bar for absolute.
- kg/cm² is the technical atmosphere (at), not standard atmospheres.
Contact & corrections
Questions, a value that differs from your edition of the code, or an idea for a new tool. For corrections, include the standard, table and size so the value can be checked.
Or email directly:
Isometric revision compare
Compare the issued (IFC) isometric against the latest from the model. Drop two PDFs for a linework overlay, or two PCF files for a component-by-component change list. Files stay in your browser.