Expansion loop sizing
How much a hot line grows between anchors, and how long the loop legs must be to take it, by the guided cantilever method. For early layout and rack planning; the stress analysis confirms it.
Calculation verification
Every result on this page can be checked by hand. For each calculator: the inputs, the formula, a worked example with real numbers, the units, the standard it comes from, and what it does not cover. Worked examples checked against the calculator output on 17 Nov 2026.
Expansion loop sizingASME B31.3 data, guided cantilever method
Input parameters
| Parameter | Symbol | Unit | Source |
|---|---|---|---|
| NPS and schedule | D, I | mm, mm⁴ | ASME B36.10M |
| Material | E, α, S | – | B31.3 Tables C-6, C-1, A-1 |
| Design and installation temperature | T_h, T_a | °C | Design basis |
| Anchor-to-anchor length | L_a | m | Layout |
| Thermal cycles | f | – | B31.3 para. 302.3.5 stress range factor |
| Loop shape and width ratio | – | U or L; W = H/2 or H | Layout |
Formula used
Growth per metre e = (e(T_h) − e(T_a)), from Table C-1 (in/100 ft → mm/m) Total growth Δ_tot = e · L_a; each U-loop leg takes Δ = Δ_tot / 2 (L-bend: Δ = Δ_tot) S_A = f (1.25 S_c + 0.25 S_h) Leg length L = √(3 E D Δ / S_A) (guided cantilever) H = max(L, 3D) rounded up to 100; W = H/2 or H Check: σ = 3 E D Δ / H²; anchor force F = 12 E I Δ / H³
Worked example
NPS 6 Sch 40 carbon steel (A106 B), 21 °C to 250 °C, 60 m between anchors, U-loop, f = 1.0, W = H/2.
- Table C-1 at 482 °F: 3.45 in/100 ft; at 70 °F: 0 → e = 2.88 mm/m
- Δ_tot = 2.88 × 60 = 173 mm; each leg Δ = 86.4 mm
- S_c = 20 ksi = 137.9 MPa; S_h (482 °F) = 19.1 ksi = 131.7 MPa → S_A = 1.25 × 137.9 + 0.25 × 131.7 = 205.3 MPa
- L = √(3 × 203 400 × 168.3 × 86.4 / 205.3) = 6574 mm
- H = 6600 mm (rounded up to 100); W = 3300 mm
- σ = 3 × 203 400 × 168.3 × 86.4 / 6600² = 204 MPa (99% of S_A); anchor force ≈ 8.6 kN
Result: Loop height H = 6 600 mm, width W = 3 300 mm (preliminary).
Units
- Internally mm, MPa, °C; shown in mm/m, mm, MPa, kN (or inch units)
Standard or engineering basis
- ASME B31.3: para. 302.3.5 (S_A), Table C-1 (expansion), Table C-6 (E), Table A-1 (S)
- Guided cantilever method: M.W. Kellogg, Design of Piping Systems
Assumptions and limitations
- Preliminary layout and space reservation only. Formal stress analysis is still required.
- Bend flexibility, friction, branch connections and nozzle loads are ignored.
- Free ends are assumed guided; temperatures are limited to the table range (to 800 °F / 427 °C).
- Only three materials are included; values are interpolated from the tables as published.
Contact & corrections
Questions, a value that differs from your edition of the code, or an idea for a new tool. For corrections, include the standard, table and size so the value can be checked.
Or email directly:
Isometric revision compare
Compare the issued (IFC) isometric against the latest from the model. Drop two PDFs for a linework overlay, or two PCF files for a component-by-component change list. Files stay in your browser.