Pipe Ref
Units

Expansion loop sizing

How much a hot line grows between anchors, and how long the loop legs must be to take it, by the guided cantilever method. For early layout and rack planning; the stress analysis confirms it.

Calculation verification

Every result on this page can be checked by hand. For each calculator: the inputs, the formula, a worked example with real numbers, the units, the standard it comes from, and what it does not cover. Worked examples checked against the calculator output on 17 Nov 2026.

Expansion loop sizingASME B31.3 data, guided cantilever method

Input parameters

ParameterSymbolUnitSource
NPS and scheduleD, Imm, mm⁴ASME B36.10M
MaterialE, α, S–B31.3 Tables C-6, C-1, A-1
Design and installation temperatureT_h, T_a°CDesign basis
Anchor-to-anchor lengthL_amLayout
Thermal cyclesf–B31.3 para. 302.3.5 stress range factor
Loop shape and width ratio–U or L; W = H/2 or HLayout

Formula used

Growth per metre e = (e(T_h) − e(T_a)), from Table C-1 (in/100 ft → mm/m)
Total growth Δ_tot = e · L_a;  each U-loop leg takes Δ = Δ_tot / 2 (L-bend: Δ = Δ_tot)
S_A = f (1.25 S_c + 0.25 S_h)
Leg length  L = √(3 E D Δ / S_A)   (guided cantilever)
H = max(L, 3D) rounded up to 100;  W = H/2 or H
Check: σ = 3 E D Δ / H²;  anchor force F = 12 E I Δ / H³

Worked example

NPS 6 Sch 40 carbon steel (A106 B), 21 °C to 250 °C, 60 m between anchors, U-loop, f = 1.0, W = H/2.

  1. Table C-1 at 482 °F: 3.45 in/100 ft; at 70 °F: 0 → e = 2.88 mm/m
  2. Δ_tot = 2.88 × 60 = 173 mm; each leg Δ = 86.4 mm
  3. S_c = 20 ksi = 137.9 MPa; S_h (482 °F) = 19.1 ksi = 131.7 MPa → S_A = 1.25 × 137.9 + 0.25 × 131.7 = 205.3 MPa
  4. L = √(3 × 203 400 × 168.3 × 86.4 / 205.3) = 6574 mm
  5. H = 6600 mm (rounded up to 100); W = 3300 mm
  6. σ = 3 × 203 400 × 168.3 × 86.4 / 6600² = 204 MPa (99% of S_A); anchor force ≈ 8.6 kN

Result: Loop height H = 6 600 mm, width W = 3 300 mm (preliminary).

Units

  • Internally mm, MPa, °C; shown in mm/m, mm, MPa, kN (or inch units)

Standard or engineering basis

  • ASME B31.3: para. 302.3.5 (S_A), Table C-1 (expansion), Table C-6 (E), Table A-1 (S)
  • Guided cantilever method: M.W. Kellogg, Design of Piping Systems

Assumptions and limitations

  • Preliminary layout and space reservation only. Formal stress analysis is still required.
  • Bend flexibility, friction, branch connections and nozzle loads are ignored.
  • Free ends are assumed guided; temperatures are limited to the table range (to 800 °F / 427 °C).
  • Only three materials are included; values are interpolated from the tables as published.