Pipe Ref Ask a question
Units

Instrument tag decoder

Type an instrument tag from a P&ID, like FIC-101, PDIT-2034A or LAHH-3301, and read what each letter means, the loop number, and what the piping designer has to allow for. Letters follow the ISA-5.1 identification scheme.

Try:

How a tag is built

The first letter is what is measured. An optional second letter changes it (D = differential, Q = totalised). The letters after that say what the instrument does, in the order indicator/recorder first, then the output. All instruments in one control loop share the loop number, so FT-101, FIC-101 and FCV-101 belong together.

First letter: what is measured

LetterVariableNotes
AAnalysisComposition or property, e.g. O₂, pH, H₂S, conductivity analysers
BBurner, combustionFlame detection and burner management
CUser's choiceDefined in the project legend; often conductivity
DUser's choiceDefined in the project legend; often density
EVoltageElectrical potential
FFlowFlow rate
GUser's choiceDefined in the project legend; often gauging or position
HHandStarted by a person: hand switch, hand valve
ICurrentElectrical current
JPowerElectrical power
KTimeTime or schedule
LLevelLiquid or interface level
MUser's choiceDefined in the project legend; often moisture
NUser's choiceDefined in the project legend
OUser's choiceDefined in the project legend
PPressurePressure or vacuum
QQuantityCounted or totalised quantity
RRadiationRadiation
SSpeedSpeed or frequency
TTemperatureTemperature
UMultivariableSeveral variables in one loop
VVibrationVibration or mechanical analysis
WWeightWeight or force
XUnclassifiedMeaning given in the project legend; XV is the usual on/off valve
YEventEvent, state or presence
ZPositionPosition or dimension, e.g. valve open/closed

Second letter as a modifier

LetterModifierExample
DDifferentialPDT, TDI: difference between two points
FRatioFFIC: ratio of two flows
JScanTJI: one indicator scanning several points
KRate of changeTKI: how fast the variable is changing
QTotaliseFQI: flow added up over time
SSafetyOnly in PSV, PSE, TSV, TSE: self-acting safety devices
XX-axisVibration direction
YY-axisVibration direction
ZZ-axisVibration direction

Following letters: what it does

LetterFunctionMeaning
AAlarmAlarm
BUser's choiceDefined in the project legend
CControllerControl: acts on the process
EElementPrimary element: the sensor in the process
GGaugeGlass or gauge you look at directly
IIndicatorShows the value
KControl stationManual/auto station
LLightPilot light
NUser's choiceDefined in the project legend
OOrificeRestriction orifice
PPointTest or sample connection
RRecorderRecords the value
SSwitchSwitch: on/off output at a set point
TTransmitterSends the signal to the control system
UMultifunctionSeveral functions in one device
VValveValve, damper or louver
WWellThermowell or probe pocket
XUnclassifiedMeaning given in the project legend
YRelayRelay, compute or convert, e.g. I/P converter, solenoid
ZActuatorDriver or actuator
HHighAfter A or S, e.g. LAH, PSLL (HH = high-high)
LLowAfter A or S, e.g. LAH, PSLL (HH = high-high)
MMiddleAfter A or S, e.g. LAH, PSLL (HH = high-high)

Common tags on P&IDs

  • Pressure indicator (gauge)
  • Pressure transmitter
  • Pressure indicating transmitter
  • Differential pressure indicating transmitter
  • Pressure indicating controller
  • Pressure control valve
  • Pressure safety valve
  • Rupture disc
  • Pressure alarm high-high
  • Pressure switch low-low
  • Temperature indicator (thermometer)
  • Temperature element
  • Thermowell
  • Temperature transmitter
  • Temperature indicating controller
  • Temperature control valve
  • Thermal relief valve
  • Flow element
  • Flow transmitter
  • Flow indicating controller
  • Flow control valve
  • Restriction orifice
  • Flow totalising indicator
  • Flow relay / I/P converter
  • Level gauge (gauge glass)
  • Level transmitter
  • Level indicating controller
  • Level control valve
  • Level alarm high
  • Level switch low-low
  • Analyser transmitter
  • On/off valve
  • Hand valve
  • Hand switch
  • Valve open / closed limit switch
  • Position transmitter

Instrument bubbles

In the fieldControl roomBehind panel InstrumentDCSComputerPLC

The shape says what kind of device it is: a circle for a standalone instrument, a circle in a square for a DCS display or control, a hexagon for a computer function and a diamond in a square for a PLC. No line means the device is in the field. A solid line means it is in the main control room, where the operator can reach it. A dashed line means it is behind the panel or in a rack the operator does not normally use.

Letter meanings follow the ISA-5.1 identification letters, summarised in our own words. Many projects add their own tags (SDV, BDV, MOV). The project legend sheet always wins.