Instrument tag decoder
Type an instrument tag from a P&ID, like FIC-101, PDIT-2034A or LAHH-3301, and read what each letter means, the loop number, and what the piping designer has to allow for. Letters follow the ISA-5.1 identification scheme.
How a tag is built
The first letter is what is measured. An optional second letter changes it (D = differential, Q = totalised). The letters after that say what the instrument does, in the order indicator/recorder first, then the output. All instruments in one control loop share the loop number, so FT-101, FIC-101 and FCV-101 belong together.
First letter: what is measured
| Letter | Variable | Notes |
|---|---|---|
| A | Analysis | Composition or property, e.g. O₂, pH, H₂S, conductivity analysers |
| B | Burner, combustion | Flame detection and burner management |
| C | User's choice | Defined in the project legend; often conductivity |
| D | User's choice | Defined in the project legend; often density |
| E | Voltage | Electrical potential |
| F | Flow | Flow rate |
| G | User's choice | Defined in the project legend; often gauging or position |
| H | Hand | Started by a person: hand switch, hand valve |
| I | Current | Electrical current |
| J | Power | Electrical power |
| K | Time | Time or schedule |
| L | Level | Liquid or interface level |
| M | User's choice | Defined in the project legend; often moisture |
| N | User's choice | Defined in the project legend |
| O | User's choice | Defined in the project legend |
| P | Pressure | Pressure or vacuum |
| Q | Quantity | Counted or totalised quantity |
| R | Radiation | Radiation |
| S | Speed | Speed or frequency |
| T | Temperature | Temperature |
| U | Multivariable | Several variables in one loop |
| V | Vibration | Vibration or mechanical analysis |
| W | Weight | Weight or force |
| X | Unclassified | Meaning given in the project legend; XV is the usual on/off valve |
| Y | Event | Event, state or presence |
| Z | Position | Position or dimension, e.g. valve open/closed |
Second letter as a modifier
| Letter | Modifier | Example |
|---|---|---|
| D | Differential | PDT, TDI: difference between two points |
| F | Ratio | FFIC: ratio of two flows |
| J | Scan | TJI: one indicator scanning several points |
| K | Rate of change | TKI: how fast the variable is changing |
| Q | Totalise | FQI: flow added up over time |
| S | Safety | Only in PSV, PSE, TSV, TSE: self-acting safety devices |
| X | X-axis | Vibration direction |
| Y | Y-axis | Vibration direction |
| Z | Z-axis | Vibration direction |
Following letters: what it does
| Letter | Function | Meaning |
|---|---|---|
| A | Alarm | Alarm |
| B | User's choice | Defined in the project legend |
| C | Controller | Control: acts on the process |
| E | Element | Primary element: the sensor in the process |
| G | Gauge | Glass or gauge you look at directly |
| I | Indicator | Shows the value |
| K | Control station | Manual/auto station |
| L | Light | Pilot light |
| N | User's choice | Defined in the project legend |
| O | Orifice | Restriction orifice |
| P | Point | Test or sample connection |
| R | Recorder | Records the value |
| S | Switch | Switch: on/off output at a set point |
| T | Transmitter | Sends the signal to the control system |
| U | Multifunction | Several functions in one device |
| V | Valve | Valve, damper or louver |
| W | Well | Thermowell or probe pocket |
| X | Unclassified | Meaning given in the project legend |
| Y | Relay | Relay, compute or convert, e.g. I/P converter, solenoid |
| Z | Actuator | Driver or actuator |
| H | High | After A or S, e.g. LAH, PSLL (HH = high-high) |
| L | Low | After A or S, e.g. LAH, PSLL (HH = high-high) |
| M | Middle | After A or S, e.g. LAH, PSLL (HH = high-high) |
Common tags on P&IDs
- Pressure indicator (gauge)
- Pressure transmitter
- Pressure indicating transmitter
- Differential pressure indicating transmitter
- Pressure indicating controller
- Pressure control valve
- Pressure safety valve
- Rupture disc
- Pressure alarm high-high
- Pressure switch low-low
- Temperature indicator (thermometer)
- Temperature element
- Thermowell
- Temperature transmitter
- Temperature indicating controller
- Temperature control valve
- Thermal relief valve
- Flow element
- Flow transmitter
- Flow indicating controller
- Flow control valve
- Restriction orifice
- Flow totalising indicator
- Flow relay / I/P converter
- Level gauge (gauge glass)
- Level transmitter
- Level indicating controller
- Level control valve
- Level alarm high
- Level switch low-low
- Analyser transmitter
- On/off valve
- Hand valve
- Hand switch
- Valve open / closed limit switch
- Position transmitter
Instrument bubbles
The shape says what kind of device it is: a circle for a standalone instrument, a circle in a square for a DCS display or control, a hexagon for a computer function and a diamond in a square for a PLC. No line means the device is in the field. A solid line means it is in the main control room, where the operator can reach it. A dashed line means it is behind the panel or in a rack the operator does not normally use.
Letter meanings follow the ISA-5.1 identification letters, summarised in our own words. Many projects add their own tags (SDV, BDV, MOV). The project legend sheet always wins.