List the lines that run on the rack. Each line is sorted into process, utility or fire water from its name, and you can change it. Choose cable trays and future space, then download the cross-section as PDF or DXF.
Calculation verification
Every result on this page can be checked by hand. For each calculator: the inputs, the formula, a worked example with real numbers, the units, the standard it comes from, and what it does not cover. Worked examples checked against the calculator output on 17 Nov 2026.
Pipe rack widthLayout practice using pipe and flange OD
Input parameters
| Parameter | Symbol | Unit | Source |
|---|---|---|---|
| Each line: NPS, class, insulation, type | OD, F, ins | mm | B36.10M OD; B16.5 / B16.47 Series A flange OD |
| Flanges insulated or boxed | – | yes / no | Insulation specification |
| Cable trays | nE, nI, w | nos, mm | Electrical / instrument trays |
| Future space | f | % | Project basis |
| Widest rack allowed | Wmax | mm | Layout limit; more lines go to another tier |
| First tier elevation | EL₁ | mm | Top of steel from grade |
Formula used
Line envelope: env = max(OD/2 + ins, F/2 + ins if flanges insulated) Neighbours: cc = max(OD/2 + ins + OD′/2 + ins′ + 25, flange + OD′/2 + ins′ + 25), rounded up to 10 mm Tier width = 300 (column) + 2 × 100 (edge) + env(first) + env(last) + Σ cc along each side + cc between the two inner lines Future = tier width × f, rounded up to 100; rack width = largest tier + future, rounded up to 500 (column C/C) Tier spacing = max(1500, largest line envelope incl. shoe + 750, rounded up to 250) Trays: 300 + 200 + n·w + (n − 1)·150 per group, + 300 between electrical and instrument
Worked example
Two process lines on one tier: NPS 8 Class 150 with 40 mm insulation, NPS 6 Class 300 bare. Flanges insulated, 25% future, no trays.
- Line 1: OD 219.1, flange OD 342.9 → env = max(109.6 + 40, 171.5 + 40) = 211.5 mm
- Line 2: OD 168.3, flange OD 317.5 → env = 158.8 mm
- cc = max(109.6 + 40 + 84.1 + 25 = 258.7, 211.5 + 84.1 + 25 = 320.6, 158.8 + 149.6 + 25 = 333.3) = 333.3 → 340 mm
- Tier = 300 + 200 + 211.5 + 158.8 + 340 = 1210.2 mm (one line next to each column)
- Future = 1210.2 × 25% = 302.6 → 400 mm; total 1610.2 → rounded up to 2000 mm
Result: Rack width 2 000 mm column C/C.
Units
- mm throughout; elevations in mm from grade
Standard or engineering basis
- Pipe OD: ASME B36.10M; flange OD: ASME B16.5 (NPS ≤ 24) and B16.47 Series A (NPS 26–48)
- Line arrangement and allowances follow common EPC pipe rack practice (largest lines at the columns, future space in the middle, utilities above process, flare at the top outside). They are not code requirements.
Assumptions and limitations
- A first-pass width for layout studies, not a structural design.
- Clearances (25 mm), column width (300), edge (100) and tray gaps (150) are typical values; use your project standard.
- Line loads, beam sizes, branch connections, valves on the rack, expansion loops and access are not checked.
- Flanges on neighbouring lines are assumed staggered.
Contact & corrections
Questions, a value that differs from your edition of the code, or an idea for a new tool. For corrections, include the standard, table and size so the value can be checked.
Or email directly:
Isometric revision compare
Compare the issued (IFC) isometric against the latest from the model. Drop two PDFs for a linework overlay, or two PCF files for a component-by-component change list. Files stay in your browser.