Control valve station layout: block, bypass and drain valves

A control valve wears out and needs calibration, so the piping around it must let maintenance isolate it, drain it, take it out and, if the process needs it, keep running on a bypass.

Block valveBlock valveReducerReducer Control valveGlobe valve on the bypassDrainDrain Flow →
A typical station in elevation. The bypass can also run beside the main line, in plan.

What a station contains

  • Block valves either side, usually line size, so the control valve can be isolated.
  • Reducers: the control valve is often one or two sizes smaller than the line. Put the reducers right at the valve so the smaller size runs only as far as it has to.
  • Drains between each block valve and the control valve, so the trapped section can be emptied and depressured before the valve is opened up. Add a vent where the section can trap gas.
  • Bypass with a globe valve, because the operator throttles flow by hand while the control valve is out. It is usually sized at least as large as the control valve.

Is a bypass always needed?

No. The P&ID decides. Bypasses are left off where the plant can stop to change the valve, where spare valves are installed instead, and on shutdown or safety-related valves, where a bypass would let someone defeat the protection.

Layout rules

  • Stem vertical, actuator up on horizontal lines where possible. It keeps the packing and actuator in their best position and makes removal easier.
  • Keep it low. Put the station at grade or on a platform so the handwheel, positioner and drains can be reached without a ladder. Use the valve height in your project specification.
  • Face the positioner to the access side, and leave room above the actuator to lift it off.
  • Removal: the valve comes out between two flanges. Allow enough flexibility, or a removable spool, so the flanges can be spread, and support the pipe on both sides so it does not sag when the valve is out.
  • No pockets: keep the bypass beside or above the main line so it drains, and keep the bypass branch connections close to the block valves to avoid dead legs.
  • Flow direction: check the arrow on the valve body against the P&ID.

Common mistakes

  • Block valves so close to the control valve that its bolts cannot be pulled.
  • Drains missing on one side, so the valve body cannot be emptied.
  • Actuator height not checked against the pipe rack or platform above.

For bypass above, beside or below, vertical, angle, three-way and other arrangements, with drawings and limits, see control valve station layout types.

Common questions

Why is the bypass valve a globe valve?

Because it is used to throttle flow by hand while the control valve is out. A globe valve throttles well; a gate valve does not.

Should the control valve be smaller than the line?

Often it is, because it is sized for its pressure drop, not for the line. The reducers go right at the valve.

Can a control valve be installed with the stem horizontal?

Many can, but stem-vertical with the actuator up is preferred. Check with the valve supplier for large actuators.