Pressure gauge and transmitter tapping points

Most bad pressure readings come from the tapping, not the instrument: a tap in the wrong place fills with gas, liquid or dirt, and the gauge reads it faithfully.

Gas: topLiquid, steam: sideup to 45° belowBottom: avoid, dirt collects Transmitter aboveGas: lines drain backTapTransmitter belowLiquid: lines stay full
Where to take a tap from a horizontal line, and where to put the transmitter.

The root valve

Every tap starts with a root valve at the pipe, often ¾ in or ½ in to the piping specification. It isolates the whole instrument connection. Transmitters then usually have an instrument valve or a manifold: 2-valve for pressure, 3- or 5-valve for differential pressure.

Which side of the pipe

ServiceTap on a horizontal lineInstrument
Gas, vapourTop, so liquid drains back to the pipeAbove the tap
LiquidSide, from horizontal to about 45° below, so gas does not collectBelow the tap
SteamSideBelow the tap, with the lines full of condensate
AnyNot the bottom: dirt and sediment collect there

On vertical lines any position around the pipe works.

Impulse lines

  • Keep them short and slope them steadily, often 1 in 12, with no pockets.
  • For differential pressure, run both lines together so they see the same temperature.
  • Heat-trace them where the fluid can freeze or thicken.

Where along the line

  • Away from turbulence: not right after an elbow, valve or pump discharge flange where you can avoid it.
  • On pumps, the discharge gauge usually sits between the pump and the check valve, so it shows the pump pressure.
  • Readable: gauge faces towards the walkway, at a height that can be read from grade or a platform.

Accessories

  • Siphon (pigtail) on steam, so condensate protects the gauge from live steam.
  • Snubber where pressure pulses, for example on reciprocating pumps.
  • Diaphragm seal for corrosive, viscous or solidifying fluids.

Common questions

Why are gas taps on top of the pipe?

So any liquid that condenses in the impulse line runs back into the pipe instead of sitting in the line and giving a false reading.

Why is the transmitter below the tap on liquid service?

So the impulse lines stay full of liquid. Gas bubbles trapped in a liquid line shift the reading.

What is a root valve?

The first isolation valve at the pipe, where the instrument connection starts.

More guides

Still have a doubt?Ask Pipe Ref. Clear questions get a reply, and the best ones become new guides, without your name.
Ask a question

General engineering guidance for learning and early design. Your project specifications and the governing code edition always take precedence.