Pipe Ref
Units

P&ID valve symbols: how to read them

Almost every valve on a P&ID starts from the same shape: two triangles meeting point to point. What is added in the middle, on top or filled in tells you which valve it is.

The symbols

These are the common conventions, based on ISA-5.1 and typical project legend sheets. Every project has its own legend, so always check it first; small differences (especially for check and butterfly valves) are normal.

ValveSymbolHow to recognise it
Gate valve (also the generic valve)Two triangles point to point. Many legends use it for any manual isolation valve.
Globe valveThe same, with a filled dot in the middle.
Ball valveAn open circle in the middle.
Check (non-return) valveOne triangle filled, usually with a flow arrow. Some legends draw a Z or a slash instead.
Butterfly valveA line through the middle (the disc on its shaft). Variants are common.
Plug valveA small solid block in the middle.
Needle valveA pointed stem above the body.
Normally closed valveBoth triangles filled, or the valve marked NC. Locked or car-sealed valves add LO, LC, CSO or CSC.
Angle valveOne triangle on the run, one turned down: the flow turns 90° inside the valve.
Three-way valveThree triangles meeting at the centre.
Control valveA valve body with a stem and an actuator on top; the dome is a diaphragm actuator. Fail action is shown as FO, FC or FL.
Relief valve (PSV)An angle body with a spring on top: inlet from below or the side, outlet at 90°.

Marks you will see next to valves

  • NO / NC: normally open or normally closed in operation.
  • LO / LC: locked open or locked closed. CSO / CSC: car-sealed open or closed, typically on relief valve isolation.
  • FO / FC / FL: on control valves, what the valve does if the air or power fails: fail open, fail closed, fail last position.
  • Size and spec breaks: a valve can sit where the line size or piping class changes; the break is drawn next to it.

Reading a valve on a line

  1. Find the shape, then the mark in the middle or on top.
  2. Check the tag: control and relief valves carry an instrument tag (for example FV-101, PSV-101); manual valves usually do not.
  3. Look for NC, LO or CSO marks, and for a spec break.
  4. Follow the flow arrow for check and relief valves; they only work one way.

Common questions

What is the symbol for a check valve on a P&ID?

Most legends draw the two-triangle valve body with one triangle filled, often with a flow arrow. Some use a Z shape or a slash. The project legend sheet decides.

How do you show a normally closed valve?

Fill both triangles, or write NC next to the valve. Locked or car-sealed valves add LC or CSC.

How is a ball valve different from a globe valve on a P&ID?

A ball valve has an open circle in the middle; a globe valve has a small filled dot.

More guides

General engineering guidance for learning and early design. Your project specifications and the governing code edition always take precedence.